What is best way to wire a ceiling receptacle in this situation? Planned maintenance scheduled April 23, 2019 at 23:30 UTC (7:30pm US/Eastern) Announcing the arrival of Valued Associate #679: Cesar Manara Unicorn Meta Zoo #1: Why another podcast?How do I wire a switch/receptacle combination?Is there some kind of adapter for an old ceiling box?Rewiring a switch controlled receptacle to a ceiling lightOddball wiring for ceiling lightWhat is the purpose of these removable “collars” on ceramic light fixturesHow close can light be to exposed insulation?Convert light fixture to receptacleWill cutting section of 2x4 reduce strengthWiring a ceiling light to a switched receptacleRunning wire in basement with drop ceiling

Strange behavior of Object.defineProperty() in JavaScript

What is the chair depicted in Cesare Maccari's 1889 painting "Cicerone denuncia Catilina"?

Lagrange four-squares theorem --- deterministic complexity

How does light 'choose' between wave and particle behaviour?

Putting class ranking in CV, but against dept guidelines

What would you call this weird metallic apparatus that allows you to lift people?

What does 丫 mean? 丫是什么意思?

How does Belgium enforce obligatory attendance in elections?

How can I prevent/balance waiting and turtling as a response to cooldown mechanics

How much damage would a cupful of neutron star matter do to the Earth?

What's the point of the test set?

Random body shuffle every night—can we still function?

Trademark violation for app?

Sum letters are not two different

How to compare two different files line by line in unix?

An adverb for when you're not exaggerating

What does Turing mean by this statement?

Did Mueller's report provide an evidentiary basis for the claim of Russian govt election interference via social media?

How do living politicians protect their readily obtainable signatures from misuse?

How fail-safe is nr as stop bytes?

Project Euler #1 in C++

Deconstruction is ambiguous

What do you call the main part of a joke?

How to write capital alpha?



What is best way to wire a ceiling receptacle in this situation?



Planned maintenance scheduled April 23, 2019 at 23:30 UTC (7:30pm US/Eastern)
Announcing the arrival of Valued Associate #679: Cesar Manara
Unicorn Meta Zoo #1: Why another podcast?How do I wire a switch/receptacle combination?Is there some kind of adapter for an old ceiling box?Rewiring a switch controlled receptacle to a ceiling lightOddball wiring for ceiling lightWhat is the purpose of these removable “collars” on ceramic light fixturesHow close can light be to exposed insulation?Convert light fixture to receptacleWill cutting section of 2x4 reduce strengthWiring a ceiling light to a switched receptacleRunning wire in basement with drop ceiling



.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;








1















I was trying to rewire this garage door opener where in current situation it is not code compliant to where it is. The picture above shows where a porcelain light socket was wired. I had hoped to use it for receptacle but the cover is too big for the box and the one that does fit is too recessed in ceiling. Behind the middle of box in picture is cross piece that is mounted between two ceiling joists. I had thought of keeping light and make another hole in ceiling for receptacle box. How close could the porcelain light fixture and receptacle be to each other to be code compliant? Using Led bulb in socket and both are on same circuit.enter image description here










share|improve this question






























    1















    I was trying to rewire this garage door opener where in current situation it is not code compliant to where it is. The picture above shows where a porcelain light socket was wired. I had hoped to use it for receptacle but the cover is too big for the box and the one that does fit is too recessed in ceiling. Behind the middle of box in picture is cross piece that is mounted between two ceiling joists. I had thought of keeping light and make another hole in ceiling for receptacle box. How close could the porcelain light fixture and receptacle be to each other to be code compliant? Using Led bulb in socket and both are on same circuit.enter image description here










    share|improve this question


























      1












      1








      1








      I was trying to rewire this garage door opener where in current situation it is not code compliant to where it is. The picture above shows where a porcelain light socket was wired. I had hoped to use it for receptacle but the cover is too big for the box and the one that does fit is too recessed in ceiling. Behind the middle of box in picture is cross piece that is mounted between two ceiling joists. I had thought of keeping light and make another hole in ceiling for receptacle box. How close could the porcelain light fixture and receptacle be to each other to be code compliant? Using Led bulb in socket and both are on same circuit.enter image description here










      share|improve this question
















      I was trying to rewire this garage door opener where in current situation it is not code compliant to where it is. The picture above shows where a porcelain light socket was wired. I had hoped to use it for receptacle but the cover is too big for the box and the one that does fit is too recessed in ceiling. Behind the middle of box in picture is cross piece that is mounted between two ceiling joists. I had thought of keeping light and make another hole in ceiling for receptacle box. How close could the porcelain light fixture and receptacle be to each other to be code compliant? Using Led bulb in socket and both are on same circuit.enter image description here







      electrical wiring receptacle






      share|improve this question















      share|improve this question













      share|improve this question




      share|improve this question








      edited 1 hour ago









      Machavity

      8,46821942




      8,46821942










      asked 2 hours ago









      georgia-guygeorgia-guy

      1149




      1149




















          2 Answers
          2






          active

          oldest

          votes


















          2














          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here






          share|improve this answer























          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago


















          0














          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.






          share|improve this answer























          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            1 hour ago











          • The link is too long but search Home Depot for "4" Round Old Work Electrical Ceiling Box" and check out the old-work boxes. Make sure if you buy one you can get the correct receptacle cover for it. I think the 4 inch or 4-O (O as in oh, not the number zero) boxes are the only ones that they make a receptacle cover to fit. It will be a metal commercial cover. I don't think the 3-1/2 inch will have a cover, but I could be wrong. Home Depot can show you what they have.

            – lqlarry
            15 mins ago












          Your Answer








          StackExchange.ready(function()
          var channelOptions =
          tags: "".split(" "),
          id: "73"
          ;
          initTagRenderer("".split(" "), "".split(" "), channelOptions);

          StackExchange.using("externalEditor", function()
          // Have to fire editor after snippets, if snippets enabled
          if (StackExchange.settings.snippets.snippetsEnabled)
          StackExchange.using("snippets", function()
          createEditor();
          );

          else
          createEditor();

          );

          function createEditor()
          StackExchange.prepareEditor(
          heartbeatType: 'answer',
          autoActivateHeartbeat: false,
          convertImagesToLinks: false,
          noModals: true,
          showLowRepImageUploadWarning: true,
          reputationToPostImages: null,
          bindNavPrevention: true,
          postfix: "",
          imageUploader:
          brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
          contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
          allowUrls: true
          ,
          noCode: true, onDemand: true,
          discardSelector: ".discard-answer"
          ,immediatelyShowMarkdownHelp:true
          );



          );













          draft saved

          draft discarded


















          StackExchange.ready(
          function ()
          StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162387%2fwhat-is-best-way-to-wire-a-ceiling-receptacle-in-this-situation%23new-answer', 'question_page');

          );

          Post as a guest















          Required, but never shown

























          2 Answers
          2






          active

          oldest

          votes








          2 Answers
          2






          active

          oldest

          votes









          active

          oldest

          votes






          active

          oldest

          votes









          2














          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here






          share|improve this answer























          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago















          2














          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here






          share|improve this answer























          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago













          2












          2








          2







          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here






          share|improve this answer













          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered 2 hours ago









          MachavityMachavity

          8,46821942




          8,46821942












          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago

















          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago
















          I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

          – georgia-guy
          1 hour ago





          I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

          – georgia-guy
          1 hour ago













          Unless you think that light circuit is overloaded, this should be good enough to run a door opener

          – Machavity
          1 hour ago





          Unless you think that light circuit is overloaded, this should be good enough to run a door opener

          – Machavity
          1 hour ago













          0














          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.






          share|improve this answer























          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            1 hour ago











          • The link is too long but search Home Depot for "4" Round Old Work Electrical Ceiling Box" and check out the old-work boxes. Make sure if you buy one you can get the correct receptacle cover for it. I think the 4 inch or 4-O (O as in oh, not the number zero) boxes are the only ones that they make a receptacle cover to fit. It will be a metal commercial cover. I don't think the 3-1/2 inch will have a cover, but I could be wrong. Home Depot can show you what they have.

            – lqlarry
            15 mins ago
















          0














          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.






          share|improve this answer























          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            1 hour ago











          • The link is too long but search Home Depot for "4" Round Old Work Electrical Ceiling Box" and check out the old-work boxes. Make sure if you buy one you can get the correct receptacle cover for it. I think the 4 inch or 4-O (O as in oh, not the number zero) boxes are the only ones that they make a receptacle cover to fit. It will be a metal commercial cover. I don't think the 3-1/2 inch will have a cover, but I could be wrong. Home Depot can show you what they have.

            – lqlarry
            15 mins ago














          0












          0








          0







          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.






          share|improve this answer













          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered 1 hour ago









          lqlarrylqlarry

          7,18711336




          7,18711336












          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            1 hour ago











          • The link is too long but search Home Depot for "4" Round Old Work Electrical Ceiling Box" and check out the old-work boxes. Make sure if you buy one you can get the correct receptacle cover for it. I think the 4 inch or 4-O (O as in oh, not the number zero) boxes are the only ones that they make a receptacle cover to fit. It will be a metal commercial cover. I don't think the 3-1/2 inch will have a cover, but I could be wrong. Home Depot can show you what they have.

            – lqlarry
            15 mins ago


















          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            1 hour ago











          • The link is too long but search Home Depot for "4" Round Old Work Electrical Ceiling Box" and check out the old-work boxes. Make sure if you buy one you can get the correct receptacle cover for it. I think the 4 inch or 4-O (O as in oh, not the number zero) boxes are the only ones that they make a receptacle cover to fit. It will be a metal commercial cover. I don't think the 3-1/2 inch will have a cover, but I could be wrong. Home Depot can show you what they have.

            – lqlarry
            15 mins ago

















          It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

          – georgia-guy
          1 hour ago





          It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

          – georgia-guy
          1 hour ago













          The link is too long but search Home Depot for "4" Round Old Work Electrical Ceiling Box" and check out the old-work boxes. Make sure if you buy one you can get the correct receptacle cover for it. I think the 4 inch or 4-O (O as in oh, not the number zero) boxes are the only ones that they make a receptacle cover to fit. It will be a metal commercial cover. I don't think the 3-1/2 inch will have a cover, but I could be wrong. Home Depot can show you what they have.

          – lqlarry
          15 mins ago






          The link is too long but search Home Depot for "4" Round Old Work Electrical Ceiling Box" and check out the old-work boxes. Make sure if you buy one you can get the correct receptacle cover for it. I think the 4 inch or 4-O (O as in oh, not the number zero) boxes are the only ones that they make a receptacle cover to fit. It will be a metal commercial cover. I don't think the 3-1/2 inch will have a cover, but I could be wrong. Home Depot can show you what they have.

          – lqlarry
          15 mins ago


















          draft saved

          draft discarded
















































          Thanks for contributing an answer to Home Improvement Stack Exchange!


          • Please be sure to answer the question. Provide details and share your research!

          But avoid


          • Asking for help, clarification, or responding to other answers.

          • Making statements based on opinion; back them up with references or personal experience.

          To learn more, see our tips on writing great answers.




          draft saved


          draft discarded














          StackExchange.ready(
          function ()
          StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162387%2fwhat-is-best-way-to-wire-a-ceiling-receptacle-in-this-situation%23new-answer', 'question_page');

          );

          Post as a guest















          Required, but never shown





















































          Required, but never shown














          Required, but never shown












          Required, but never shown







          Required, but never shown

































          Required, but never shown














          Required, but never shown












          Required, but never shown







          Required, but never shown







          Popular posts from this blog

          Are there any AGPL-style licences that require source code modifications to be public? Planned maintenance scheduled April 23, 2019 at 23:30 UTC (7:30pm US/Eastern) Announcing the arrival of Valued Associate #679: Cesar Manara Unicorn Meta Zoo #1: Why another podcast?Force derivative works to be publicAre there any GPL like licenses for Apple App Store?Do you violate the GPL if you provide source code that cannot be compiled?GPL - is it distribution to use libraries in an appliance loaned to customers?Distributing App for free which uses GPL'ed codeModifications of server software under GPL, with web/CLI interfaceDoes using an AGPLv3-licensed library prevent me from dual-licensing my own source code?Can I publish only select code under GPLv3 from a private project?Is there published precedent regarding the scope of covered work that uses AGPL software?If MIT licensed code links to GPL licensed code what should be the license of the resulting binary program?If I use a public API endpoint that has its source code licensed under AGPL in my app, do I need to disclose my source?

          2013 GY136 Descoberta | Órbita | Referências Menu de navegação«List Of Centaurs and Scattered-Disk Objects»«List of Known Trans-Neptunian Objects»

          Button changing it's text & action. Good or terrible? The 2019 Stack Overflow Developer Survey Results Are Inchanging text on user mouseoverShould certain functions be “hard to find” for powerusers to discover?Custom liking function - do I need user login?Using different checkbox style for different checkbox behaviorBest Practices: Save and Exit in Software UIInteraction with remote validated formMore efficient UI to progress the user through a complicated process?Designing a popup notice for a gameShould bulk-editing functions be hidden until a table row is selected, or is there a better solution?Is it bad practice to disable (replace) the context menu?